Carlo Gavazzi EM210-72D Panel or DIN Rail Meter with Modbus RS485 (EM21072DAV53XOSX)
£189.72
£227.66 inc. VAT
£160.00
£192.00 inc. VAT
IME Conto D4-PT Meter provides a cost-effective solution for remote monitoring by Pulse or Modbus communications.
Reference three-phase voltage Un | 100V and 400V |
Specified operating range | ± 15%Un |
Power consumption in voltage circuit (max. voltage) | 0,2VA for phase |
Reference frequency | 50-60Hz |
Tolerance | 49...61Hz |
Basic current, Ib | 5A |
Max. current, Imax | 6A |
Starting current | 10mA |
Rated value Uaux ac | 230V (single phase, neutral-phase) |
Tolerance | 0,85...1,15Uaux |
Rated Frequency | 50Hz |
Working Frequency | 47...63Hz |
Power consumption in supply circuit (max. voltage) | 4,5VA(2,2)W at 264V |
Contact range | 110Vdc/ac – 50mA |
Pulse weight | electable 1 imp/10Wh – 100Wh – 1kWh – 10kWh - 100kWh - 1MWh |
Pulse duration | Selectable 50 – 100 – 200 – 300ms |
Installation category | III |
Pollution degree | 2 |
Insulation voltage rating | 300V Phase-earth |
Reference temperature | 23°C ± 2°C |
Specified operating range | -25...55°C |
Limit range fpr storage and transport | -25...70°C |
Max.power dissipation | ≤ 4W (for switchboard thermal calculation) |
Mechanical environment | M1 |
Electromagnetic environment | E2 |
Housing | 4 module DIN 43880 |
Connections | Screw on terminals |
Mounting | Snap-on 35mm rail |
Rail Type | Top hat TH35-15 (EN60715) |
Protection degree (EN60529) | IP51 front frame, IP20 terminals (IP51 mounting the KWH-meter on a IP51 switchboard) |
Weight | 260 grams |
Our Knowledge Base section provides in-depth guides on metering related topics, and can aid you in the process of buying the right product.
Find out moreOur in-house product experts are at hand to help you find the right products and solutions for your projects.
01423 340 000 Start live chat