Limited A1140-DC is available at low cost from stock - click here to purchase for next day delivery

Inepro PRO2-S Single Phase 100A DC MID Energy Meter

Inepro PRO2-S Single Phase 100A DC MID Energy Meter

£48.96

£58.75 inc. VAT

Product Description

The PRO2 series is a range of single phase energy meters consisting of 4 different types. They are available in a standard, M-bus or Modbus version. All meter types are equipped with an infrared interface and a selectable pulse output.

PRO2 energy meters display a number of instantaneous variables like voltage, current, active power, reactive power, apparent power, frequency and power factor on the LCD and via the different communication options. For calculating the total energy usage, there are 7 calculation modes available. All forward (import) and reverse (export) (re)active energy values are stored in different meter registers.

The PRO2 energy meters have an exceptional combination of a high accuracy class (1/B) for active energy measurement and a broad temperature range.

All meters comply with the Measuring Instruments Directive 2014/32/EU. The MID approval ensures the accuracy and quality of the meter and enables its use in billing purposes.

Specification

General

Casing

PC flame resistant plastic

Nominal voltage (Un)

230V AC

Operational voltage

195-253VAC

Insulation capabilities

•AC voltage withstand = 4KV for 1 minute

• Impulse voltage withstand = 6KV – 1,2μS waveform

Base current Ib

5A

Maximum rated current (Imax)

100A

Operational current range

0,4%Ib-Imax

Overcurrent withstand

30Imax for 0,01s

Operational frequency range

50Hz ±10%

Internal power consumption

≤1W/Phase - ≤1VA/Phase

Test output flash rate (RED LED)

10.000 imp/kWh

Pulse output rate

10.000/2.000/1.000/100/10/1/0,1/0,01 imp/kWh

Pulse width

• 1.000/100/10/1/0,1/0,01 imp/kWh = 31ms

• 2.000 imp/kWh < 30kW = 31ms

• 2.000 imp/kWh > 30kW = 15ms

• 10.000 imp/kWh < 6kW = 31ms

• 10.000 imp/kWh > 6kW = 15ms

• 10.000 imp/kWh > 12kW = 5ms

Data store

The data can be stored for more than 10 years without power

Infrared Specification

Infrared wavelengths

900- 1000nm

Communication Distance

Direct contact

Protocol

IEC62056-21:2002 (IEC1107)

Environmental

Operating humidity

≤ 75%

Storage humidity

≤ 95%

Operating temperature

-40°C - +70°C

International standard

EN50470-1/3

Accuracy class

B (=1% accuracy)

Protection against penetration of dust and water

IP51

Insulating encased meter of protective class

II

Dimensions

Height without protective cover

92,5 mm

Height

141,5 mm

Width

35,8 mm

Depth

63 mm

Max. diameter power connection clamps

35 mm² (solid copper)

Weight

0,16 Kg (net)

Downloads

Ask an expert about the
PRO2-S

Help & Advice

Knowledge Base

Knowledge Base

Our Knowledge Base section provides in-depth guides on metering related topics, and can aid you in the process of buying the right product.

Find out more

Our Products

addressarrow-leftcaret-downcaret-leftcaret-rightmenuorderpadlockpdf