Limited A1140-DC is available at low cost from stock - click here to purchase for next day delivery

Socomec DIRIS A-40 Multi-Function Modbus Meter (4825-0500)

Socomec DIRIS A-40 Multi-Function Modbus Meter (4825-0500)

£557.72

£669.26 inc. VAT

Product Description

Socomec's DIRIS A-40 is a panel-mounted power monitoring device (PMD). The meter offers a range of functions for measuring voltage, current, power, energy and quality. It also allows for the analysis of a single-phase or three-phase load.

Product Features:
  • CL0.2 accuracy
  • Autocorrect current transformer
  • Configuration wizard set-up
  • THD Measurement up to 63rd

Specification

Auxiliary Power Supply

Alternative Voltage

110/400 VAC or 120/300 VDC - Cat III

Frequency

50/60 Hz

Power Consumption

5VA AC / 1,5VA DC

Connection

Removable spring-cage terminal block, 2x 2 positions, 0.5 - 2.5 mm2 solid cable or 0.25 - 1.5 mm² stranded cable with end piece

Power and Energy Measurement

Accuracy

Active energy and active power

0.2 DIRIS A-40 class only

Class 0.5 with TE, TF or iTR sensors

Class 1 with TR sensors

Accuracy of reactive energy

Class 2 with TE, TR or TF sensors

Power Factor Measurement

Accuracy

Class 0.5 with TE, TF or iTR sensors

Class 1 with TR sensors

Voltage Measurement

Characteristics of the network measured

50-300VAC (Ph/N) - 87-520VAC (Ph/Ph) - CATIII

Frequency range

45 to 65Hz

Frequency accuracy

Class 0.02

Network type

Single-phase/ Two-phase / Two-phase with neutral / Three-phase / Three-phase with neutral

Measurement by voltage transformer

Primary: 400 000 VAC

Secondary: 60, 100, 110, 173, 190 VAC

Input consumption

≤0,1VA

Accuracy of voltage measurement

Class 0.2

Connection

Removable spring-cage terminal block,
4 positions, 0.5 - 2.5 mm² solid cable
or 0.25 - 1.5 mm² stranded cable with end piece

Current Measurement

Number of current inputs

3

Associated current sensors

Solid TE, split-core TR, flexible TF current sensors

Accuracy

0.2 DIRIS A-40 class only

Class 0.5 with TE, TF or iTR sensors

Class 1 with TR sensors

Connection

Specific Socomec cable with RJ12 connectors

Input Characteristics

Number

3

Type / Power supply

Optocoupler with internal (12 VDC ± 10%) or external (12-24 VDC ± 20%) polarisation

Input function

Logic status, status of circuit breaker, synchronization topography, multifluid pulse metering

Connection

Removable screw terminal block, 5 positions, stranded or solid 0.14 - 1.5 mm² cable

Output Characteristics

Number

2

Type

Optocoupler 30 Vd.c. max 20mA max - SELV

Output function

Command, energy pulse output, load sheeding, alarm

Connection

Removable screw terminal block, 4 positions, stranded or solid 0.14 - 1.5 mm² cable

Communication Characteristics

Link

RS485

Connection type

2 to 3 half duplex wires

Protocol

Modbus RTU

Baud rate

1200 to 115 200 baud

USB

Configuration of DIRIS A-40

Downloads