** Our office will close at 5pm on Friday the 20th December with normal service resuming on Thursday the 2nd of January 2025 **

Socomec COUNTIS E16 80A Direct Connected Single Phase Dual-Tariff MID Energy Meter with M-Bus (4850-3046)

Socomec COUNTIS E16 80A Direct Connected Single Phase Dual-Tariff MID Energy Meter with M-Bus (4850-3046)

£200.80

£240.96 inc. VAT

Product Description

Socomec's COUNTIS E16 is a modular active electrical energy meter displaying the energy and power consumed (kWh and kW) directly on its back-lit LCD display. It is designed for single-phase load metering and is used for direct connections of up to 80 A.

Product Features:
  • Dimensions: 2 DIN Modules wide
  • Dual Tariff options
  • Pulse Output communication

Specification

Case

Type

modular

Number of modules

2

Dimensions (W x H x D)

36 x 90 x 64 mm

Case degree of protection

IP20

Front degree of protection

IP51

Display type

backlit LCD

Rigid cable cross-section

1.5 to 35mm²

Flexible cable cross-section

1.5 to 35mm²

Weight

215 g E13/E14/E17/E18
205 g E11/E12/E15/E16

Current Measurement

Type

single-phase direct 80 A

Input consumption

0.5 VA per phase

Startup current (Ist)

20 mA

Minimum current (Imin)

0.25 A

Transition current (Itr)

0.5A

Reference current (Iref)

5 A

Permanent overload (Imax)

80A

Intermittent overload

30 Imax over 10 ms

Voltage Measurement

Range of measurement

230 ... 400V +/- 20 %

Consumption (VA)

3.5 VA max E13/E14/E17/E18
7.5 VA max E11/E12/E15/E16

Permanent overload

290V phase-neutral

Energy Accuracy

Active (according to IEC 62053-21)

Class 1

Active (according to EN 50470)

Class B

Reactive (according to IEC 62053-22)

Class 2

Power Supply

Self-supplied

Yes

Frequency

50 / 60 Hz

Output (pulsed)

Optoisolated type (IEC 62053-31)

250 VAC/DC - 100 mA (E11/E12)
27 VDC - 27 mA (E13/E14/E15/E16)

Number

1

Fixed pulse weight

100 Wh

Pulse duration

50 ± 2 ms ON time
30 ± 2 ms OFF time

Operating temperature

Operating temperature

-20 to 55 °C

Storage temperature

-20 to 75 °C

Relative temperature

80%

Communication

Communication

E13/E14

E15/E16

E17/E18

Link

RS485WiredRJ45

Type

2 to 3 half duplex2 half duplexFull Duplex

Protocol

MODBUS RTUM-BUSMODBUS TCP, HTTP, NTP, DHCP

Baudrate

1200 … 115200 bauds300 … 9600 bauds10/100 Mbps

Downloads

Ask an expert about the
Socomec COUNTIS E16

Help & Advice

Knowledge Base

Knowledge Base

Our Knowledge Base section provides in-depth guides on metering related topics, and can aid you in the process of buying the right product.

Find out more

Our Products